Skip to content

Design Mode

Purpose

In Design mode, the cooling tower calculates the required Merkel number (KaV/L) to achieve a specified water outlet temperature. This is the mode used when sizing a new tower or evaluating whether a given set of conditions is feasible.


Required Inputs

Parameter Description Typical Range
Inlet Water Temperature From the connected water stream 30 - 60 °C
Desired Outlet Temperature Target cold water temperature 20 - 40 °C
Air Dry-Bulb Temperature Ambient air temperature 15 - 45 °C
Air Wet-Bulb Temperature Ambient wet-bulb (or RH) 10 - 35 °C
L/G Ratio Water-to-air mass flow ratio 0.5 - 2.5
Atmospheric Pressure Local barometric pressure 90,000 - 105,000 Pa
Calculation Method Merkel or Poppe

Step-by-Step Procedure

  1. Create and connect streams: Place the Cooling Tower on the flowsheet. Connect a material stream as the water inlet (hot water). Connect another material stream as the water outlet.

  2. Configure the inlet stream: Set the water inlet temperature, mass flow rate, and pressure. Assign a property package (e.g., Steam Tables or NRTL).

  3. Open the Cooling Tower editor by double-clicking the unit operation.

  4. Set Calculation Mode to Design.

  5. Set Calculation Method to Merkel or Poppe.

  6. Enter air conditions:

    • Set the Air Dry-Bulb Temperature (e.g., 25 °C)
    • Set the Air Wet-Bulb Temperature (e.g., 20 °C) — or switch to Relative Humidity input
  7. Set L/G Ratio (e.g., 1.0).

  8. Set Desired Outlet Temperature (e.g., 30 °C).

  9. Run the calculation (Ctrl+F5 or the Solve button).


Outputs

After a successful calculation, Design mode produces:

Output Description
Required KaV/L The Merkel number needed to achieve the target outlet temperature
Cooling Range Tw,in - Tw,out
Approach Tw,out - Twb
Tower Efficiency Range / (Range + Approach)
Heat Rejected Q = mw * Cpw * Range
Evaporation Rate Water lost by evaporation
Makeup Water Rate Total water replacement needed
Fan Power Based on air pressure drop and efficiency

Design Guidelines

Practical L/G Selection

  • L/G = 0.75 - 1.5: Typical for induced-draft towers
  • L/G < 0.8: Large air flow, lower KaV/L but higher fan power
  • L/G > 2.0: Small air flow, higher KaV/L and more difficult to achieve

Feasibility Check

If the calculated KaV/L exceeds approximately 3.0 - 4.0, the design may be impractical. Consider:

  • Increasing the L/G ratio (reducing air flow)
  • Relaxing the approach (higher outlet temperature)
  • Using a more efficient fill type

Example

Given: Tw,in = 40 °C, Tw,out = 30 °C, Tdb = 25 °C, Twb = 20 °C, L/G = 1.0, mw = 1 kg/s

Results (Merkel method):

Parameter Value
Required KaV/L 0.803
Range 10.0 K
Approach 10.0 K
Efficiency 50.0%
Heat Rejected 41.8 kW