Parameters Reference
Air Conditions
Parameter
Property Name
Default
Units
Description
Air Dry-Bulb Temperature
Air Dry-Bulb Temperature
298.15
K
Ambient air temperature
Air Wet-Bulb Temperature
Air Wet-Bulb Temperature
293.15
K
Ambient wet-bulb temperature
Air Relative Humidity
Air Relative Humidity
0.6
fraction
Alternative to wet-bulb (0 to 1)
Atmospheric Pressure
Atmospheric Pressure
101325
Pa
Local barometric pressure
Humidity Input
You can specify air humidity via either wet-bulb temperature or relative humidity. Select the input type in the editor. When using RH, the wet-bulb temperature is calculated internally and displayed read-only.
Tower Configuration
Parameter
Property Name
Default
Units
Description
Calculation Method
Calculation Method
0 (Poppe)
enum
0 = Poppe, 1 = Merkel
Calculation Mode
Calculation Mode
0 (Rating)
enum
0 = Rating, 1 = Design
L/G Ratio
L/G Ratio
1.0
dimensionless
Water-to-air mass flow ratio
KaV/L (Merkel Number)
KaV/L (Merkel Number)
1.5
dimensionless
Tower characteristic (Rating mode)
Desired Outlet Temperature
Desired Outlet Temperature
303.15
K
Target cold water temp (Design mode)
Fill Parameters
Parameter
Property Name
Default
Units
Description
Fill C1
Fill C1
0.9
—
Correlation coefficient
Fill C2
Fill C2
-0.55
—
Correlation exponent
Fill correlation: \( KaV/L = C_1 \times (L/G)^{C_2} \)
Water Balance
Parameter
Property Name
Default
Units
Description
Drift Loss %
Drift Loss Percent
0.1
%
Drift as % of circulation
Cycles of Concentration
Cycles of Concentration
5.0
—
For blowdown calculation
Fan
Parameter
Property Name
Default
Units
Description
Air Pressure Drop
Air Pressure Drop
200
Pa
Pressure drop across tower
Fan Efficiency
Fan Efficiency
0.75
fraction
Fan mechanical efficiency
Numerical
Parameter
Property Name
Default
Units
Description
Number of Increments
Number of Increments
50
—
Integration steps (Simpson/RK4)
Output Parameters (Read-Only)
Water Outlet
Parameter
Property Name
Units
Description
Water Outlet Temperature
Water Outlet Temperature
K
Cold water temperature
Cooling Range
Cooling Range
K
Tw,in - Tw,out
Approach
Approach
K
Tw,out - Twb
Tower Efficiency
Tower Efficiency
fraction
Range / (Range + Approach)
Heat Rejected
Heat Rejected
W
Total heat rejection
Air Outlet
Parameter
Property Name
Units
Description
Air Outlet Temperature
Air Outlet Temperature
K
Exhaust air temperature
Air Outlet Humidity Ratio
Air Outlet Humidity Ratio
kg/kg
Exhaust air moisture content
Air Outlet Relative Humidity
Air Outlet Relative Humidity
fraction
Exhaust air RH
Air Mass Flow Rate
Air Mass Flow Rate
kg/s
Dry air mass flow
Water Balance
Parameter
Property Name
Units
Description
Evaporation Rate
Evaporation Rate
kg/s
Water lost by evaporation
Drift Loss Rate
Drift Loss Rate
kg/s
Water lost as droplets
Blowdown Rate
Blowdown Rate
kg/s
Intentional water discharge
Makeup Water Rate
Makeup Water Rate
kg/s
Total water replacement
Parameter
Property Name
Units
Description
Calculated KaV/L
Calculated KaV/L
—
Merkel number (from calculation)
Fan Power
Fan Power
W
Fan energy consumption
Unit Conversions
All internal calculations use SI units (K, Pa, kg/s, W). The DWSIM editor automatically converts to/from the user's selected unit system using SharedClasses.SystemsOfUnits.Converter.
Quantity
SI Unit
Common Alternatives
Temperature
K
°C, °F, °R
Pressure
Pa
kPa, bar, atm, inHg, mmHg
Mass flow
kg/s
kg/h, lb/h, t/h
Power
W
kW, hp, BTU/h
Enthalpy
kJ/kg
BTU/lb, cal/g