Parameters Reference

Input Parameters (Read-Write)

Air Conditions

Parameter Property Name Default Units Description
Air Dry-Bulb Temperature Air Dry-Bulb Temperature 298.15 K Ambient air temperature
Air Wet-Bulb Temperature Air Wet-Bulb Temperature 293.15 K Ambient wet-bulb temperature
Air Relative Humidity Air Relative Humidity 0.6 fraction Alternative to wet-bulb (0 to 1)
Atmospheric Pressure Atmospheric Pressure 101325 Pa Local barometric pressure

Humidity Input

You can specify air humidity via either wet-bulb temperature or relative humidity. Select the input type in the editor. When using RH, the wet-bulb temperature is calculated internally and displayed read-only.

Tower Configuration

Parameter Property Name Default Units Description
Calculation Method Calculation Method 0 (Poppe) enum 0 = Poppe, 1 = Merkel
Calculation Mode Calculation Mode 0 (Rating) enum 0 = Rating, 1 = Design
L/G Ratio L/G Ratio 1.0 dimensionless Water-to-air mass flow ratio
KaV/L (Merkel Number) KaV/L (Merkel Number) 1.5 dimensionless Tower characteristic (Rating mode)
Desired Outlet Temperature Desired Outlet Temperature 303.15 K Target cold water temp (Design mode)

Fill Parameters

Parameter Property Name Default Units Description
Fill C1 Fill C1 0.9 Correlation coefficient
Fill C2 Fill C2 -0.55 Correlation exponent

Fill correlation: \( KaV/L = C_1 \times (L/G)^{C_2} \)

Water Balance

Parameter Property Name Default Units Description
Drift Loss % Drift Loss Percent 0.1 % Drift as % of circulation
Cycles of Concentration Cycles of Concentration 5.0 For blowdown calculation

Fan

Parameter Property Name Default Units Description
Air Pressure Drop Air Pressure Drop 200 Pa Pressure drop across tower
Fan Efficiency Fan Efficiency 0.75 fraction Fan mechanical efficiency

Numerical

Parameter Property Name Default Units Description
Number of Increments Number of Increments 50 Integration steps (Simpson/RK4)

Output Parameters (Read-Only)

Water Outlet

Parameter Property Name Units Description
Water Outlet Temperature Water Outlet Temperature K Cold water temperature
Cooling Range Cooling Range K Tw,in - Tw,out
Approach Approach K Tw,out - Twb
Tower Efficiency Tower Efficiency fraction Range / (Range + Approach)
Heat Rejected Heat Rejected W Total heat rejection

Air Outlet

Parameter Property Name Units Description
Air Outlet Temperature Air Outlet Temperature K Exhaust air temperature
Air Outlet Humidity Ratio Air Outlet Humidity Ratio kg/kg Exhaust air moisture content
Air Outlet Relative Humidity Air Outlet Relative Humidity fraction Exhaust air RH
Air Mass Flow Rate Air Mass Flow Rate kg/s Dry air mass flow

Water Balance

Parameter Property Name Units Description
Evaporation Rate Evaporation Rate kg/s Water lost by evaporation
Drift Loss Rate Drift Loss Rate kg/s Water lost as droplets
Blowdown Rate Blowdown Rate kg/s Intentional water discharge
Makeup Water Rate Makeup Water Rate kg/s Total water replacement

Performance

Parameter Property Name Units Description
Calculated KaV/L Calculated KaV/L Merkel number (from calculation)
Fan Power Fan Power W Fan energy consumption

Unit Conversions

All internal calculations use SI units (K, Pa, kg/s, W). The DWSIM editor automatically converts to/from the user's selected unit system using SharedClasses.SystemsOfUnits.Converter.

Quantity SI Unit Common Alternatives
Temperature K °C, °F, °R
Pressure Pa kPa, bar, atm, inHg, mmHg
Mass flow kg/s kg/h, lb/h, t/h
Power W kW, hp, BTU/h
Enthalpy kJ/kg BTU/lb, cal/g