Skip to content

Rating Mode

Purpose

In Rating mode, the cooling tower predicts the water outlet temperature for a tower with known characteristics (KaV/L). This mode is used to evaluate the performance of an existing tower under different operating conditions.


Required Inputs

Parameter Description Typical Range
Inlet Water Temperature From the connected water stream 30 - 60 °C
KaV/L (Merkel Number) Known tower characteristic 0.5 - 5.0
Air Dry-Bulb Temperature Ambient air temperature 15 - 45 °C
Air Wet-Bulb Temperature Ambient wet-bulb (or RH) 10 - 35 °C
L/G Ratio Water-to-air mass flow ratio 0.5 - 2.5
Atmospheric Pressure Local barometric pressure 90,000 - 105,000 Pa
Calculation Method Merkel or Poppe

KaV/L from Design Mode

You can obtain the KaV/L from a previous Design mode calculation, from manufacturer data, or from fill correlation:

\[ KaV/L = C_1 \times (L/G)^{C_2} \]

where \( C_1 \) and \( C_2 \) are fill-specific constants (configurable in the editor).


Step-by-Step Procedure

  1. Set Calculation Mode to Rating.

  2. Enter the known KaV/L value (e.g., 0.8144).

  3. Configure air conditions (Tdb, Twb) and L/G ratio.

  4. Run the calculation.

The solver uses bisection to find the outlet temperature that produces the specified KaV/L. The convergence tolerance is 0.0001 K.


Outputs

Output Description
Water Outlet Temperature Predicted cold water temperature
Cooling Range Tw,in - Tw,out
Approach Tw,out - Twb
Tower Efficiency Range / (Range + Approach)
Heat Rejected Q = mw * Cpw * Range
Air Outlet Temperature Temperature of exhaust air
Air Outlet Humidity Humidity ratio of exhaust air
Evaporation Rate Water lost by evaporation

Design-Rating Round-Trip Consistency

One important validation is the round-trip test: a Design calculation produces a KaV/L, which is then used as input for a Rating calculation. The Rating result should reproduce the original outlet temperature.

Example:

Step Mode Input Output
1 Design Tw,out = 30.00 °C KaV/L = 0.8144
2 Rating KaV/L = 0.8144 Tw,out = 30.00 °C

Verified

The DWSIM implementation achieves 0.00 K deviation in the Design-Rating round-trip for both Merkel and Poppe methods (see Internal Validation).


Performance Curves

Rating mode is particularly useful for generating performance curves — how the outlet temperature varies with changing conditions:

  • Variable wet-bulb: How does tower performance change seasonally?
  • Variable L/G: What happens if the water flow rate changes?
  • Variable Tw,in: How does the tower respond to process upsets?

These analyses can be automated using the Automation API.